GR50I-ZID.GL.CR-116905/A01

Type GR50I-ZID.GL.CR
Item number 116905/A01
Designation Ventilation unit with backward curved impeller.
Measurement data
3~380-480 V 50/60 Hz P1 4.60 kW 7.40-6.00 A
2150 min-1 40 °C
ErP data
ErP measurement category: A
Air flow rate qv at Eta opt: 9635 m³/h
Pressure increase pfs at Eta opt: 1221 Pa
Input power P1 at Eta opt: 4650 W
Efficiency ηstatA: 75.1 %
Efficiency rating: Nactual = 78.6 / Ntarget = 62*
*ErP 2015
Minimum operating temperature -20 °C
Thermal class 155
Efficiency class IE5
Motor protection integrated active temperature management
Protection type IP55
Impregnation protection against moisture and hot climates
Bearing quality ball bearings with long-life lubrication
Mass 54 kg

Scroll to Top