Type D2E160-AH02-15
Motor M2E074-LA
Phase 1~ 1~
Nominal voltage VAC 230 230
Frequency Hz 50 60
Type of data definition ml ml
Valid for approval / standard – –
Speed min-1 2500 2400
Power input W 550 730
Current draw A 2.45 3.2
Motor capacitor µF 12 12
Capacitor voltage VDB 400 400
Min. back pressure Pa 400 390
Min. ambient temperature °C -25 -25
Max. ambient temperature °C 90 50
Mass 9.7 kg
Size 160 mm
Surface of rotor Coated in black
Material of impeller Sheet steel, hot-galvanised
Housing material Sheet steel, hot-galvanised
Material of guard grille Steel, phosphated and plastic-coated in white aluminium (RAL 9006)
Motor suspension Motor mounted vibration-free on both sides
Direction of rotation Counter-clockwise, seen on rotor
Type of protection IP 00
Insulation class “F”
Humidity class F2-1
Max. permissible ambient motor
temp. (transp./ storage) + 80 °C
Min. permissible ambient motor
temp. (transp./storage) – 40 °C
Mounting position Shaft horizontal
Condensate discharge holes None, open rotor
Operation mode S1
Motor bearing Ball bearing
Brand |
---|