K3G310-RB01-03

Type K3G310-RB01-03
Motor M3G074-CF
Phase 1~
Nominal voltage VAC 230
Nominal voltage range VAC 200 .. 240
Frequency Hz 50/60
Method of obtaining data ml
Speed (rpm) min-1 1525
Power consumption W 150
Current draw A 1.2
Min. ambient temperature °C -25
Max. ambient temperature °C 60
Mass 8.8 kg
Size 310 mm
Motor size 74
Rotor surface Thick-film passivated
Impeller material PP plastic
Support plate material Sheet steel, galvanized
Support bracket material Steel, painted black
Number of blades 6
Direction of rotation Clockwise, viewed toward rotor
Degree of protection IP54
Insulation class “B”
Moisture (F) / Environmental (H)
protection class H1
Max. permitted ambient temp.
for motor (transport/storage) + 80 °C
Min. permitted ambient temp. for
motor (transport/storage) – 40 °C
Installation position Any
Condensation drainage holes None, open rotor
Cooling hole/opening On rotor side
Mode S1
Motor bearing Ball bearing
Technical features – Output 10 VDC, max. 10 mA
– Tach output
– Power limiter
– Motor current limitation
– Soft start
– Control input 0-10 VDC / PWM
– Control interface with SELV potential safely disconnected from the mains
– Overvoltage detection
– Thermal overload protection for electronics/motor
– Line undervoltage detection
Touch current according to IEC
60990 (measuring circuit Fig. 4,
TN system) <= 3.5 mA
Motor protection Electronic motor protection
With cable Variable
Protection class assignment I; If a protective earth is connected.
The built-in component has several local protection class assignments.
The final protection class is determined by the intended installation.
Conformity with standards EN 60335-1; CE
Approval UL 1004-7 + 60730-1; CSA C22.2 No. 77 + CAN/CSA-E60730-1; CCC

Scroll to Top